Breaker Size Calculator

Calculate breaker size from amps, watts, kW or kVA. Handles DC, single phase and three phase, the 125 percent continuous rule, standard frame rounding and conductor pairing.

https://hexacalculator.com/calculators/other/electronics/breaker-size-calculator

Other

Electronics

Breaker Size Calculator

Calculate breaker size from amps, watts, kW or kVA. Handles DC, single phase and three phase, the 125 percent continuous rule, standard frame rounding and conductor pairing.

Breaker Size Calculator

Circuit and load

Power factor only changes the answer when you enter real power in watts. Leave it at 1 for a purely resistive load.

Show conductor guidance

Pair the recommended frame with a typical copper conductor size.

Check an existing breaker

See what a breaker you already have can carry, and whether this load fits.

Your breaker size

Load current
A
Design current
A
Sizing factor applied
%
Continuous-use limit
A
Maximum continuous power
W
Spare capacity in the frame
%
Minimum conductor ampacity
A

A design current of 25 A lands on the 25 A standard frame. That frame will carry 20 A continuously, which is roughly 2400 W at your voltage.

Loading calculator…

The fuse size calculator tool converts the load in a circuit to the rated current of the device that protects this circuit. By entering the load, voltage and degree of utilization of the circuit it gives back the nearest standard fuse size which is bigger than the calculated current.

The calculations are simple. The decisive factor is to set the prerequisites correctly as many incorrect results result from this. Incorrect voltage values, wrong phase configurations or calculating continuous loads as short-term loads can lead to this.

What a fuse actually protects:

There is often a tendency to think that fuses protect electrical appliances but they do not. A fuse protects the wiring, connections and path of electricity to the appliances connected to the mains supply.

Once you understand this point, almost every rule that is mentioned later becomes clearer. It's not true that the bigger the fuse, the safer it is. A larger fuse can cause more current to flow through wires that are not capable of handling that much current. The wires will heat up and the insulation will deteriorate while the fuse does not blow.

There are three main reasons why a circuit breaker trips: an overload occurs when the current exceeds the allowable value of the circuit; a short circuit occurs when a live conductor connects directly to the neutral; and a ground fault occurs when a live conductor connects to a conductive object that should not normally carry electricity.

Calculating the size of the fuse

The calculation is done in two steps: First the value is converted into amperes, then a buffer for operating load is added and rounded up.

First step: converting the load to amperes

The required formula depends on the type of circuit. In DC circuits, current is equal to power divided by voltage.

I=PVI = \frac{P}{V}

In single-phase AC power, the power factor must be taken into account because the waveforms of current and voltage are not in phase.

I=PV×PFI = \frac{P}{V \times PF}

For balanced three-phase AC power, measured as the voltage between lines, a factor of approximately 1.732 is required.

I=P3×VLL×PFI = \frac{P}{\sqrt{3} \times V_{LL} \times PF}

If the given value represents the voltage between phase and neutral conductor, this factor is 3.

I=P3×VLN×PFI = \frac{P}{3 \times V_{LN} \times PF}

If the rated output of a device is given in kVA instead of watts, then the power factor does not have to be taken into account at all since the product of volts and amperes already contains apparent power.

I1ϕ=VAVI3ϕ=VA3×VLLI_{1\phi} = \frac{VA}{V} \qquad I_{3\phi} = \frac{VA}{\sqrt{3} \times V_{LL}}

Second step: apply a safety factor for operating load and round up.

Multiply the load current by a factor that fits the mode of operation for the circuit and select the next highest standard size which is greater than or equal to the result.

Idesign=Iload×FBreaker=next standard frameIdesignI_{design} = I_{load} \times F \qquad Breaker = \text{next standard frame} \ge I_{design}

For continuous loads a factor of 125 percent is applied. This is the most common case. A continuous load is one that runs at full current for at least three hours. Adding in a quarter ensures it stays within its thermal limits without tripping the breaker due to heat building up inside the breaker itself.

The 80 percent rule is a reversed representation of the same rule.

You will likely hear two different phrasings of this: Select the size with a 125 percent continuous load or keep the continuous load below 80 percent of the breaker's amp rating. Since the inverse of 1.25 is .80, both statements mean the same thing.

So a standard 20A breaker is suitable for continuous loads of about 16A, while a 30A breaker is suitable for about 24A. The exception to this are units marked 100 percent duty; these are properly ventilated and have the appropriate connection ratings so that they can carry the maximum current indicated on the nameplate continuously. Such units are intended for special applications; make sure you actually use one of those.

Selecting the size factor:

The default options of this tool cover most common cases.

Load type

Factor

When it applies

Non-continuous load

100%

Anything that does not run at full current for three hours

Continuous load

125%

Lighting circuits, EV charging, electric heat, commercial loads

Motor or compressor

150%

A starting point before a proper motor-protection study

Air conditioner or heat pump

175%

Where the nameplate does not give MCA and MOCP

Welder

200%

Heavy intermittent duty with a very peaky current draw

The factors for motors, air conditioners and welding machines are starting points in planning and not results of standards. Motor branch circuits have their own rules for sizing, and equipment with MCA and MOCP on the nameplate must be selected based on those values, not general formulas.

If your local regulations or design requirements dictate other safety factors, select Custom and enter the percentage directly.

Example calculation:

A continuous load factor of 125% is used in each row and a two stage calculation is performed to reduce the result down to a standard size.

Load

Load current

Design current

Frame

1,500 W space heater at 120 V

1,500 / 120 = 12.5 A

12.5 x 1.25 = 15.63 A

20 A

4,500 W water heater at 240 V

4,500 / 240 = 18.75 A

18.75 x 1.25 = 23.44 A

25 A

7.2 kW EV charger at 240 V

7,200 / 240 = 30 A

30 x 1.25 = 37.5 A

40 A

9.6 kW EV charger at 240 V

9,600 / 240 = 40 A

40 x 1.25 = 50 A

50 A

1,000 W microwave at 230 V, pf 0.72

1,000 / (230 x 0.72) = 6.04 A

6.04 x 1.25 = 7.55 A

15 A

10 kW at 480 V three-phase, pf 0.90

10,000 / (1.732 x 480 x 0.9) = 13.37 A

13.37 x 1.25 = 16.71 A

20 A

It is good to remember the lines for EV chargers. A 7.2 kW charger at 240 V draws 30 A. Since charging takes several hours, the rated current is 37.5 A. Therefore a circuit breaker of 40 A is used. This circuit breaker has a maximum continuous current rating of 32 A, which adequately covers the actual current drawn by the charger of 30 A.

Standard fuse sizes:

Since the nominal rating of a circuit breaker is fixed, the calculated value of 23.44A will never be used directly as a 23A circuit breaker. Instead it would be rounded up to the next highest available size.

Common sizes are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 A. For feeders and service equipment the size range extends to 600 A. Not all ratings are available in every region. In particular for residential distribution boards 15, 20, 30, 40, 50 A are commonly used more often.

Fit the fuse holder and the wires together.

Fuses and wiring must be selected together; they are not determined separately. The conductor must be designed for the rated current of the fuse. Otherwise, the cable will become the weakest link in the circuit that would never trip.

Breaker

Copper, 75 C

Aluminium, 75 C

15 A

14 AWG

12 AWG

20 A

12 AWG

10 AWG

25 A / 30 A

10 AWG

8 AWG

35 A / 40 A / 50 A

8 AWG

6 AWG

60 A

6 AWG

4 AWG

70 A / 80 A

4 AWG

2 AWG

100 A

3 AWG

1 AWG

125 A

1 AWG

2/0 AWG

150 A

1/0 AWG

3/0 AWG

200 A

3/0 AWG

250 kcmil

These are not specifications but only guidelines to check adequacy. The actual allowable current depends on the type of insulation, temperature rating of connectors, ambient temperature, number of conductors in the same conduit and length of cable run.

If the wiring is too long then other problems arise that cannot be solved by fuses. As voltage drop depends on the size of conductor and distance there may be unwanted voltages at the furthest points even if the circuit is correctly protected.

Other rules apply to labelling of HVAC systems.

Air conditioners, heat pumps and similar appliances are usually marked with two values: MCA and MOCP. The minimum current capacity value (MCA) determines the smallest allowable conductor size. The maximum overcurrent protection value (MOCP) indicates the size of the largest circuit breaker or fuse that can be installed.

These two values are neither operating current values nor can they be derived from general formulas. If these values are indicated on the type plate, use them as a reference. This tool can be used for loads where this data is not available.

Common mistakes:

Many errors when choosing the size of a circuit breaker are not due to arithmetical mistakes but rather false assumptions. If you want to enter 7.2 kW for example and instead enter 7.2 in the field for watts, then the result is wrong by a factor of thousand.

The choice of voltage can also make a big difference. A load with the same power rating of 4,500 W will draw 37.5 A (at 120 V) while only drawing 18.75 A (at 240 V). This difference determines whether a 50 A or 25 A circuit is required.

And there are situations that can actually lead to a fire. If a circuit breaker is constantly tripping, you should not simply try replacing it with a larger one. A tripping circuit breaker indicates a problem. First check for overloads, inrush currents, faulty appliances or inadequate wiring.

What this tool does not take into account:

This is a tool for preliminary testing of power load capacity and it is far from complete protection design.

It does not check the tripping capacity or available fault current. It also does not coordinate with upstream devices. The conductor cross-sections based on ambient temperature and conduit fill are not considered, nor do it consider requirements for AFCI or GFCI protection systems, compatibility with panel boards, or regional codes.

This tool is for planning and training purposes only. Electrical installations are subject to regulations and can be dangerous. The final selection of circuit breakers and wiring must follow applicable codes, equipment markings, and manufacturer's instructions and should be inspected by a qualified electrician or technician.

Frequently asked questions

How to calculate the size of the protective switch?

Convert the load to amperage, multiply by a factor that fits the type of operation (100% for non-continuous loads, 125% for continuous loads), and select the next highest standard size circuit breaker. A continuous load of 32 amps results in a rating of 40 amps, so a 40 amp circuit breaker is used.

What is the 80% rule for circuit breakers?

The continuous load a standard breaker can handle must not exceed the rated value by less than 80 percent. So a 20-A breaker can handle about 16 A all day long. This is in line with the rule that the size of the continuous load be chosen at 125 percent. If you divide 1 by 1.25, you get 0.80.

What power in watts can a 20A fuse breaker handle?

At 120 V a 20 A breaker will handle an intermittent load of 2,400 W. The continuous load is about 1,920 W with the 80 percent rule. At 240 V these values double assuming that wiring and equipment ratings are adequate, resulting in 4,800 W and 3,840 W respectively.

Can a 20A breaker be replaced with a 30A breaker?

It is not possible to just replace the breaker. First you need to make sure that the wiring, connections and all connected devices are capable of handling 30A. Also 12 AWG wire does not meet code for a 20A circuit. If your breaker keeps tripping then look for an overload, inrush current or faulty device instead of installing a larger size.

Does the size of a fuse depend on voltage?

When the voltage changes, so does the current and when the current changes, so does the size of the circuit breaker. At constant power, if the voltage doubles, then the current will be roughly halved. The nominal voltage for the actual circuit breaker must be checked separately. It needs to be compatible with your system but is not calculated here.

What is the difference between an MCA and a MOCP?

MCA (Minimum Circuit Ampacity) is the minimum allowable current rating for a conductor that can be used in an appliance. MOCP (Maximum Overcurrent Protection) is the maximum size of circuit breaker or fuse that can be used in an appliance. If both these values are listed on the nameplate of an HVAC unit, they determine the wiring configuration. They are not determined by a general load calculation.

Related calculators

Disclaimer: This calculator is provided for general informational and educational purposes only. Our calculators are under active development, and results may be inaccurate, incomplete, or unsuitable for your situation. Always verify the figures independently and seek advice from a qualified professional before relying on them. We make no warranties and accept no liability for any loss or decision arising from use of this tool.

References

  1. NFPA 70: National Electrical Code

    The US standard behind the 125 percent continuous-load factor (Article 210.20) and the next-standard-size rule (Article 240.4).

  2. IEC 60364: Low-voltage electrical installations

    The international installation standard used outside North America for protection and conductor coordination.

  3. Wikipedia: Circuit breaker

    Background on how overcurrent protective devices operate and are rated.

  4. Wikipedia: American wire gauge

    Reference for the AWG sizes used in the conductor pairing table.